Manual
Double Sheet Detector R1000 series E20
B0046991 / Rev. 1.6
Communication with the PLC
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
89
6.3.5 External zero adjust (via PLC inputs)
This function may be required for special applications. It is, however, switched off in the standard
factory adjustment. If required it can be activated according chapter “7. Start-up“.
Note During Zero adjust no sheet must be in front of the sensor.
OUT0
IN0-1, 3-10
Enable
1
> 30ms
2
OUT3
OUT2
IN2
Zero adjust
3
4
< 30ms
5
> 30ms
OUT1
6
< 7 sec.
0-sheet
1-sheet
2-sheet